Location and Access
- Confirm the extinguisher is in its assigned location
- Check nothing blocks the path to it or hides it from view
- Make sure it is mounted on its bracket or in its cabinetUnder NFPA 10, units up to 40 lb should be mounted with the top no higher than 5 ft above the floor.
- Check the cabinet opens easily and any break glass is intact
Signage and Labels
- Check the location sign is in place where the unit is hard to see
- Make sure the operating instructions on the label face out
- Confirm the label is readable and not peeling or faded
Pressure, Pin and Seal
- Check the pressure gauge needle is in the green zoneCO2 units have no gauge. Check them by weight against the full weight stamped on the valve or label.
- Confirm the safety pin is in place
- Confirm the tamper seal is intact
- Lift the unit to check it feels full
Physical Condition
- Look for dents, cracks or other damage to the cylinder
- Check for rust or corrosion on the cylinder, valve and bracket
- Check the hose for cracks, cuts or blockage
- Make sure the nozzle is clear of dirt, nests or debris
- Look for leaks or powder residue around the valve and nozzle
- Check the handle and lever are not bent or broken
Tag and Test Dates
- Initial and date the inspection tag for this month
- Check the last annual maintenance date is within 12 monthsOSHA requires the annual maintenance date to be recorded. It is usually on the back of the tag.
- Check the hydrostatic test date on the cylinder or labelWater, foam and CO2 units are usually due every 5 years. Most stored-pressure dry chemical units are due every 12 years.
- Note when the next 6-year maintenance is due for dry chemical units
Right Class for the Hazard
- Confirm Class A coverage for wood, paper, cloth and trash
- Confirm Class B coverage near flammable liquids and gases
- Confirm Class C rating near energized electrical equipmentNever use a water extinguisher on a live electrical fire.
- Use a Class D unit for combustible metals such as magnesium
- Use a Class K unit in commercial kitchens with deep fryers
Inspection Log
- Building / floor / location: ____
- Extinguisher ID or serial number: ____ Type and size: ____
- Date: ____ Pass / Fail: ____
- Problems found and action taken: ____If it fails, remove it from service and put a working unit in its place before you leave.
- Inspector name and initials: ____